HVAC, Refrigeration & Building Science Sensible & Latent Heat and Humidity Control ASHRAE Fundamentals psychrometrics; ANSI/AHAM DH-1

Dehumidifier Size (Pints per Day) Calculator

This calculator sizes a dehumidifier the way a moisture load is actually calculated: it converts your outdoor and target indoor conditions into humidity ratios, multiplies the difference by the air the space leaks in, adds occupant and ground moisture, and returns the water that has to leave the room in pints per day. It then applies a sizing allowance and rounds up to the next common nameplate capacity, because a unit rated at 65 °F and 60% relative humidity does not deliver that number in a 60 °F crawl space.

Calculator

This calculator runs in your browser. Enable JavaScript for live results — the inputs, formula and worked example below remain fully readable without it.

Inputs this calculator takes, with typical values
InputWhat to enterExample
Floor area of the spaceThe conditioned footprint the dehumidifier has to serve, not the whole house unless the air actually mixes.1200 ft²
Average ceiling heightClear height from floor to ceiling; for a crawl space use the actual crawl depth.8 ft
Air changes per hourNatural infiltration of the space. A blower-door ACH50 divided by about 20 gives a working estimate for a whole house.0.35 ACH
Outdoor design temperatureUse your local summer dehumidification design condition, not the peak dry-bulb — humidity peaks on mild wet days.85 °F
Outdoor relative humidityRelative humidity at the outdoor temperature above; 70% at 85 °F is a typical humid-summer afternoon.70 %
Indoor temperatureThe temperature the space actually sits at while the dehumidifier runs — basements and crawl spaces are often 10 °F cooler than upstairs.75 °F
Target indoor relative humidity50% is the usual comfort and mould-control target; 55–60% is the practical setpoint for an unconditioned crawl space.50 %
People normally in the spaceCount only people present while the unit runs; each seated adult adds about 200 BTU/h of latent heat.2 people
Other moisture sourcesLaundry, unvented showers, aquariums, plants, drying concrete or an uncovered crawl space floor. Leave at zero if none apply.0 pints/day
Sizing allowanceMultiplier applied before choosing a nameplate size, because rated capacity is measured at 65 °F / 60% RH and falls in cooler, drier air.1.25 ×

It returns

  • Moisture removal required — Water that must leave the space every 24 hours at the conditions you entered.
  • Capacity to specify after allowance
  • Next common nameplate size
  • Latent load
  • Infiltration airflow
  • Humidity ratio difference

The formula

pints/day=60ρCFM(WoutWtgt)24+mint1.0432
QL=mday241060

In plain text: pints/day = [60 · ρ · CFM · (W_out − W_target) · 24 + internal loads] ÷ 1.0432

  • ρDensity of dry air, taken as 0.075 (lb/ft³)
  • CFMInfiltration airflow = ACH × volume ÷ 60 (ft³/min)
  • W_outHumidity ratio of outdoor air (lb water / lb dry air)
  • W_tgtHumidity ratio at the indoor temperature and target RH (lb water / lb dry air)
  • m_intInternal moisture from occupants and listed sources (lb/day)
  • 1.0432Mass of one US liquid pint of water (lb/pint)

Humidity ratio comes from the ASHRAE saturation-pressure correlation at 14.696 psia: W = 0.621945·p_v/(P − p_v), with p_v = RH × p_ws(T).

Updated Category Sensible & Latent Heat and Humidity Control Verified against published test cases Reading time 11 min

What a dehumidifier is actually sized against

A dehumidifier is sized against a moisture balance, not against floor area. Water enters a space from three places — humid outdoor air leaking in, people and activities inside, and evaporation from wet ground or fresh concrete — and the machine has to remove all of it, every day, to hold the space at your target humidity.

Square-footage charts on retail packaging skip that balance entirely. They cannot know whether your basement leaks 20 CFM or 200, whether the crawl space floor is covered with 10-mil poly or bare clay, or whether your summers are 85 °F at 70% RH or 95 °F at 30%. Two 1,200 ft² basements in the same city can differ by a factor of four in real moisture load.

The quantity that makes the arithmetic work is humidity ratio — pounds of water vapour per pound of dry air, usually quoted in grains (7,000 grains to the pound). Relative humidity on its own tells you nothing about moisture transfer, because 70% RH at 85 °F carries roughly twice the water of 70% RH at 60 °F. If you want to see that conversion on its own, the humidity ratio calculator and the dew point calculator both work from the same psychrometric relations used here.

The formula and why it has that shape

Start with the air. Infiltration airflow is the air change rate multiplied by the volume of the space, divided by 60 to get cubic feet per minute:

CFM = ACH × area × height ÷ 60

Every cubic foot of that air carries about 0.075 lb of dry air, so 60 × 0.075 = 4.5 lb of dry air pass through per hour for each CFM. Multiply by the humidity ratio difference and you have pounds of water per hour:

lb/h = 4.5 × CFM × (W_out − W_target)

That is the same 4.5 constant that appears in the latent heat equation Q = 4,840 × CFM × ΔW, where 4,840 is 4.5 multiplied by the latent heat of vaporisation. Multiply the hourly figure by 24 for a daily load, add the internal sources, and divide by 1.0432 lb — the weight of a US liquid pint of water — to land in the units the appliance industry uses.

Occupants are handled the same way. ASHRAE lists roughly 200 BTU/h of latent gain for an adult at seated, very light activity. Divide by the 1,060 BTU/lb latent heat used here and each person contributes about 0.19 lb of water per hour, or 4.5 lb a day.

The one term you cannot calculate is evaporation from a bare earth crawl space floor, because it depends on soil moisture, ground temperature and how much of the floor is covered. That belongs in the other moisture sources field, measured rather than guessed: run a unit with a known pint counter for a week and read the number off it.

Worked example: a 1,200 ft² basement in a humid summer

Take a 1,200 ft² basement with 8 ft ceilings, leaking at 0.35 air changes per hour. Outdoors is 85 °F at 70% RH; you want 75 °F and 50% RH inside; two people are usually down there.

  1. Volume. 1,200 × 8 = 9,600 ft³.
  2. Infiltration airflow. 0.35 × 9,600 ÷ 60 = 56 CFM.
  3. Outdoor humidity ratio. At 85 °F the saturation pressure is 0.5964 psia, so pv = 0.70 × 0.5964 = 0.4175 psia and W = 0.621945 × 0.4175 ÷ (14.696 − 0.4175) = 0.01818 lb/lb, or 127.3 gr/lb.
  4. Target humidity ratio. At 75 °F the saturation pressure is 0.4302 psia, pv = 0.2151 psia, W = 0.00924 lb/lb, or 64.7 gr/lb.
  5. Difference. 127.3 − 64.7 = 62.6 gr/lb, which is 0.008946 lb/lb.
  6. Infiltration moisture. 4.5 × 56 × 0.008946 = 2.254 lb/h, and ×24 = 54.1 lb/day.
  7. Occupants. 2 × 200 ÷ 1,060 × 24 = 9.06 lb/day.
  8. Total. 54.1 + 9.06 = 63.2 lb/day ÷ 1.0432 = 60.5 pints per day.
  9. Latent load. 63.2 ÷ 24 × 1,060 = 2,790 BTU/h — about a quarter of a ton of cooling that your air conditioner is not being asked to do.
  10. Nameplate size. 60.5 × 1.25 = 75.6, so the next common size is a 80-pint unit.

Every number above is reproducible on paper from the two saturation pressures, which you can read off any psychrometric chart.

How to read the result and pick a unit

The headline pints-per-day figure is the real removal duty at the conditions you entered. The nameplate number on a dehumidifier is not the same thing. Since 2019 the US Department of Energy has required residential dehumidifiers to be rated at 65 °F and 60% relative humidity under the ANSI/AHAM DH-1 test method. Older units carry a rating taken at 80 °F and 60% RH, which is why a "70-pint" machine from 2015 and a "50-pint" machine from 2020 can be the same physical box.

Capacity falls as the air gets cooler and drier, because both the moisture available at the coil and the temperature difference driving condensation shrink. That is what the sizing allowance covers. A unit working in a 75 °F, 55% RH basement is near its rating point and 1.15–1.25 is generous; one working in a 60 °F crawl space at 55% RH is well below it, and the honest move is to read the manufacturer's performance table at your actual conditions rather than to keep inflating a multiplier.

Also check the duty cycle. A unit sized exactly to the load runs continuously, which gives the best moisture removal per kilowatt-hour but leaves no margin for a wet week. A unit sized at twice the load short-cycles, removes less water per unit of energy, and swings the humidity. Landing between 1.2 and 1.5 times the calculated load is the usual compromise.

If the space is served by air conditioning, part of this load is already being removed by the cooling coil. The condensate rate calculator shows how much, and the sensible heat ratio calculator tells you whether the coil has any latent capacity left to give.

Moisture in air at common conditions

Humidity ratio in grains of water per pound of dry air at 14.696 psia, from the ASHRAE saturation-pressure correlation. The difference between two cells is what a dehumidifier has to remove per pound of air moved.
Dry bulb30% RH50% RH60% RH70% RH80% RH
55 °F19.131.938.444.851.3
60 °F22.938.346.153.861.6
65 °F27.345.855.064.473.7
70 °F32.554.565.676.787.9
75 °F38.664.777.891.1104.4
80 °F45.676.592.1107.8123.7
85 °F53.790.2108.7127.3146.1
90 °F63.0106.1127.9150.0172.2

Read across for the outdoor condition, read your indoor target, subtract, and multiply by 4.5 × CFM to get pounds of water per hour.

Mistakes that make a dehumidifier the wrong size

  • Sizing from square feet. Area appears in this calculation only through volume, and volume only sets the infiltration airflow. A tight 2,000 ft² basement can be an easier job than a leaky 800 ft² one.
  • Comparing a pre-2019 rating to a post-2019 rating. The DOE test point moved from 80 °F to 65 °F, which cut nameplate numbers by roughly a third for the same hardware. Check which rating point a listing quotes before comparing prices.
  • Ignoring the ground. A bare crawl space floor can evaporate more water than every other source combined. A sealed vapour barrier is a cheaper fix than any machine, and it changes this calculation more than any input on the page.
  • Setting an unreachable target. A refrigerant dehumidifier struggles below about 35% RH and frosts in air below roughly 60 °F unless it has hot-gas defrost. Desiccant units cover that range and are rated differently.
  • Forgetting the sensible heat. A dehumidifier rejects both the latent heat it removes and its own compressor power into the room. Expect the space to run several degrees warmer than it did — welcome in a cool basement, unwelcome in a finished room.
  • Draining into a bucket. An 80-pint duty is a 10-gallon bucket a day. Any unit sized from this calculation needs a gravity or condensate-pump drain.

Which standards this follows

The psychrometric relations — saturation pressure over liquid water and the humidity ratio from partial pressures — are those given in the ASHRAE Handbook—Fundamentals, Chapter 1. The occupant latent gain of about 200 BTU/h for seated, very light activity is from Chapter 18. Dehumidifier capacity ratings in the United States are established under ANSI/AHAM DH-1 and the DOE test procedure at 10 CFR Part 430, which since 2019 rate residential units at 65 °F and 60% relative humidity.

When a dehumidifier is the wrong tool

Dehumidification is the last step, not the first. Three fixes beat it on cost and permanence.

Stop the water. Grading, gutters, downspout extensions and a crawl space vapour barrier remove liquid water before it ever evaporates. No appliance competes with a 10-mil poly ground cover on a dirt floor.

Stop the air. Every input on this page scales linearly with the air change rate. Halving infiltration halves the infiltration term. Air-sealing the rim joist and the crawl space vents is usually a one-day job; the air changes per hour calculator converts a blower door result into the ACH figure this page needs.

Use the cooling you already have. An air conditioner is a dehumidifier with a bigger coil. If it runs long enough, it removes the latent load for free. Short-cycling on an oversized system is the most common reason a house is cool and clammy at the same time — the latent heat load calculator shows how much moisture the coil should be taking out.

Where dehumidification genuinely earns its place is in spaces with no cooling load to piggyback on: crawl spaces, unconditioned basements, wine rooms, indoor pools, and drying-out work after a flood. In those cases size from the balance above and specify a unit with a real drain, a humidistat you trust, and a performance table published at your operating temperature.

Key terms

Humidity ratio
Pounds of water vapour per pound of dry air, often quoted in grains (7,000 gr = 1 lb). It does not change when air is heated or cooled without condensation, which is why moisture calculations use it instead of relative humidity.
Latent load
The heat associated with changing water between vapour and liquid, about 1,060 BTU per pound at room conditions. Removing 60 pints a day is a latent load of roughly 2,800 BTU/h.
AHAM rating point
The standard test condition at which a dehumidifier's pints-per-day capacity is measured — 65 °F and 60% RH under the current DOE procedure, 80 °F and 60% RH before 2019.
Air change per hour (ACH)
The number of times the full volume of a space is replaced by outdoor air in an hour. Natural infiltration in a house typically runs a small fraction of one air change per hour.

Frequently asked questions

What size dehumidifier do I need for a 1,000 square foot basement?

There is no single answer from area alone, but for a typical 8 ft basement at 0.35 air changes per hour, 85 °F and 70% RH outdoors and a 50% RH target, the load works out near 50 pints a day, which points to a 50–70 pint nameplate unit. Change any of those assumptions and the answer moves a lot: a bare dirt floor can add 20 pints a day on its own, and a tightly sealed basement can cut the number in half. Enter your own conditions above rather than relying on the area figure.

Why does a 50-pint dehumidifier now look smaller than an older 70-pint one?

The rating point changed. Until 2019 the DOE test method measured capacity at 80 °F and 60% relative humidity; the current procedure measures at 65 °F and 60% RH, where any refrigerant machine removes less water. The same physical unit that was labelled 70 pints under the old test is labelled roughly 50 pints under the new one. When you compare two units, check which test point the specification sheet quotes.

Should I size for the peak summer day or an average day?

Size for a warm, humid design day rather than the annual peak dry-bulb. Moisture loads peak on mild wet days, not the hottest afternoon — a 78 °F day at 90% RH carries more water per pound of air than a 95 °F day at 40%. Using the humid design condition and then adding the 1.2–1.5 sizing allowance leaves the unit running near-continuously in the worst week and cycling comfortably the rest of the season.

Does a dehumidifier make the room hotter?

Yes, and by more than you might expect. A dehumidifier releases the latent heat it condenses out of the air plus all of its own electrical input, and none of that leaves the room. A unit removing 60 pints a day is putting roughly 2,800 BTU/h of latent heat back as sensible heat, plus 600–700 W of compressor and fan power. In a cool basement that is a bonus; in a finished bedroom it is a reason to dehumidify with the air conditioner instead.

What relative humidity should I set it to?

50% is the standard target for occupied space and 55% is normal for a sealed crawl space. Mould growth on wood and paper needs sustained surface humidity above roughly 60%, so anything at or below 55% carries margin. Going below 40% costs disproportionate energy, offers no additional mould protection, and pushes a refrigerant unit toward coil frosting.

Can one dehumidifier serve a whole house?

Only if the air actually circulates between the spaces. A single portable unit in a basement dehumidifies the basement, not the second floor. A whole-house result needs either a ducted dehumidifier tied into the return plenum or a continuously running air handler that mixes the levels. If you are sizing a ducted unit, run this calculation on the full conditioned volume and use the whole-house infiltration rate.

How do I estimate moisture coming off a crawl space floor?

Measure it rather than estimate it. Put a unit with a pint counter or a measured bucket in the space for a week at a fixed setpoint, note the water removed per day, subtract the infiltration and occupant terms this calculator gives you, and the remainder is ground evaporation. Then enter that number in the other moisture sources field. Published per-square-foot figures for bare soil vary by an order of magnitude with soil type and water table, which is why this calculator asks you for it instead of guessing.

Why does my dehumidifier ice up in the crawl space?

Because the evaporator coil is running below freezing in air that is already cold. Standard refrigerant dehumidifiers are designed for air above roughly 60–65 °F; below that the coil surface drops under 32 °F and condensate freezes onto it, which blocks airflow and stops removal altogether. Units rated for low-temperature service use hot-gas defrost to clear the coil periodically. Below about 50 °F a desiccant dehumidifier is the correct choice, since it does not rely on condensation at all.

References

  • ASHRAE Handbook—Fundamentals, Chapter 1: Psychrometrics — American Society of Heating, Refrigerating and Air-Conditioning Engineers
  • ASHRAE Handbook—Fundamentals, Chapter 18: Nonresidential Cooling and Heating Load Calculations (occupant heat gain) — American Society of Heating, Refrigerating and Air-Conditioning Engineers
  • ANSI/AHAM DH-1, Dehumidifiers — Association of Home Appliance Manufacturers
  • 10 CFR Part 430 Subpart B, Uniform Test Method for Measuring the Energy Consumption of Dehumidifiers — U.S. Department of Energy