HVAC, Refrigeration & Building Science Refrigerant Charging & System Diagnostics ASHRAE Fundamentals psychrometrics; furnace nameplate temperature rise

HVAC Delta-T (Temperature Split) Calculator

This calculator does two jobs. In cooling mode it takes your return air dry bulb and relative humidity, works out the enthalpy drop a coil produces at your design airflow and capacity, and converts that to the dry-bulb split you should actually measure — because the correct split depends on how humid the return air is, not on a single number. In heating mode it computes the temperature rise a furnace must show at its rated output and airflow, so you can compare it to the nameplate range before you touch anything.

Calculator

This calculator runs in your browser. Enable JavaScript for live results — the inputs, formula and worked example below remain fully readable without it.

Inputs this calculator takes, with typical values
InputWhat to enterExample
ModeCooling compares supply against return; heating compares the rise across the heat exchanger against the nameplate range.Cooling — temperature split
Return air dry bulbMeasured in the return duct or at the filter grille, upstream of any leakage into the return.75 °F
Return air relative humidityFrom a digital psychrometer in the return stream; the wet bulb it implies is shown in the results.50 %
Supply air dry bulbMeasured in the supply plenum, out of line of sight of the coil.55 °F
Delivered total capacity per nominal tonNominal rating is 12,000 BTU/h per ton at AHRI conditions (80 °F DB / 67 °F WB return); delivered capacity is several percent lower when return air is cooler and drier.11000 BTU/h
Airflow per nominal tonDesign airflow across the evaporator; 400 is the usual default, 350 in humid climates and 450 in dry ones.400 CFM/ton
Relative humidity leaving the coilAir off a wet evaporator leaves close to saturation; 90–95% is the normal assumption.95 %
Supply air dry bulbMeasured in the supply plenum at least two feet downstream, where the probe cannot see the heat exchanger.125 °F
Furnace output capacityOutput, not input — the nameplate figure after the efficiency, sometimes printed as 'capacity' or 'bonnet capacity'.60000 BTU/h
Blower airflowAirflow at the heating speed tap and the measured external static pressure, from the blower table.1200 CFM

It returns

  • Measured delta-T — Return minus supply in cooling; supply minus return in heating.
  • Target delta-T
  • Measured minus target
  • Return air wet bulb
  • Supply temperature you should see

The formula

ΔTmeas=TretTsup
rise=Qout1.08CFM
h=0.240T+W(1061+0.444T)

In plain text: ΔT_measured = T_return − T_supply (cooling); target ΔT = T_return − T at which h_return − Q/(4.5·CFM) is reached

  • T_retReturn air dry-bulb temperature (°F)
  • T_supSupply air dry-bulb temperature (°F)
  • hEnthalpy of moist air per pound of dry air (BTU/lb)
  • QTotal capacity delivered per nominal ton (BTU/h)
  • CFMAirflow per nominal ton (ft³/min)

The 4.5 in the enthalpy equation is 60 min/h × 0.075 lb/ft³, the mass of dry air moved per CFM per hour.

Updated Category Refrigerant Charging & System Diagnostics Verified against published test cases Reading time 10 min

What delta-T tells you and what it does not

Delta-T is the temperature change of the air as it crosses the equipment. In cooling it is the split: return dry bulb minus supply dry bulb. In heating it is the temperature rise: supply minus return. It is the fastest whole-system check a technician has, because it needs two thermometers and no gauges.

What it measures is the ratio of sensible capacity to airflow. Rearranging the sensible heat equation, ΔT = Q_sensible ÷ (1.08 × CFM), so a wide split means high capacity or low airflow, and a narrow split means the reverse. That is why the split on its own never tells you which. It tells you that something is off and points you at the next measurement.

The trap is the single number. Technicians quote "20 degrees" as if it applied everywhere, but the correct split depends heavily on how humid the return air is. A coil pulling 12,000 BTU/h out of dry 30%-RH air spends nearly all of it lowering temperature, and the split can exceed 28 °F. The same coil pulling the same 12,000 BTU/h out of 70%-RH air spends much of it condensing water, and the split falls to about 15 °F. Both systems are working correctly.

Why the target moves with humidity

An air conditioner does not remove degrees; it removes enthalpy, the total heat content of the air including the heat locked up in water vapour. Total capacity across a coil is:

Q_total = 4.5 × CFM × Δh

where Δh is the enthalpy drop in BTU per pound of dry air and 4.5 is 60 × 0.075, the pounds of dry air moved per hour per CFM. Turn that around: if you know the capacity the coil delivers and the airflow through it, the enthalpy drop is fixed. At 11,000 BTU/h per ton and 400 CFM per ton, Δh = 11,000 ÷ (4.5 × 400) = 6.11 BTU/lb, whatever the humidity.

What is not fixed is how that 6.11 splits between temperature and moisture. Air leaving a wet evaporator sits close to saturation, around 90–95% relative humidity. So the calculation is: take the return air state, drop its enthalpy by Δh, find the temperature at which air at 95% RH has that enthalpy, and subtract. The wetter the return air, the more of the enthalpy drop goes into condensing water and the smaller the temperature change.

Furnaces are simpler, because combustion heat is entirely sensible. The rise is straight out of the sensible heat equation with no psychrometrics involved. That is also why the rise is such a good airflow measurement: with the output known from the nameplate, CFM = Q_output ÷ (1.08 × rise) gives you real airflow from two thermometers.

Worked example: a 3-ton system on a 75 °F, 50% RH day

You measure 75.0 °F and 50% RH in the return, and 55.0 °F in the supply plenum. The system is a 3-ton split running 400 CFM per ton.

  1. Measured split. 75.0 − 55.0 = 20.0 °F.
  2. Return humidity ratio. Saturation pressure at 75 °F is 0.43016 psia, so pv = 0.215 psia and W = 0.621945 × 0.215 ÷ (14.696 − 0.215) = 0.009237 lb/lb (64.7 gr/lb). That corresponds to a wet bulb of 62.6 °F.
  3. Return enthalpy. h = 0.240 × 75 + 0.009237 × (1,061 + 0.444 × 75) = 18.00 + 10.11 = 28.11 BTU/lb.
  4. Enthalpy drop. Taking 11,000 BTU/h delivered per ton at 400 CFM per ton: 11,000 ÷ (4.5 × 400) = 6.11 BTU/lb.
  5. Leaving enthalpy. 28.11 − 6.11 = 22.00 BTU/lb.
  6. Leaving temperature. Air at 95% RH reaches 22.00 BTU/lb at about 53.8 °F.
  7. Target split. 75.0 − 53.8 = 21.2 °F.

The measured 20.0 °F is 1.2 °F under target — inside normal measurement uncertainty, so the system passes this check and you stop here. Had it come out at 27 °F, the next step would be a static pressure reading; had it come out at 13 °F, the next step would be superheat and subcooling.

Reading the deviation

Treat ±3 °F as the noise band. Two field thermometers disagreeing by a degree, a probe seeing radiant heat, a slightly wrong humidity reading and a coil that is not quite at steady state will move the number by that much on a healthy system. Run the equipment for at least 15 minutes before you believe any reading.

Split wider than target. The usual cause is airflow below design: a loaded filter, a fouled evaporator, crushed flex duct, a closed damper, or a return that was never sized for the equipment. Measure total external static pressure and look the airflow up in the blower table before you touch refrigerant. A wide split can also appear on a legitimately dry day, which is exactly why this page asks for return humidity rather than assuming it.

Split narrower than target. Low refrigerant charge is the first suspect, followed by a compressor that is not pumping, airflow above design, and a room load the coil simply cannot overtake — a house at 85 °F pulling down after a hot day shows a narrow split for the first hour because the return air is hot and the coil is saturated. Take pressures and temperatures before concluding anything.

Furnace rise above the nameplate range. This is the one delta-T fault that is a safety issue rather than an efficiency one. Too little airflow across a heat exchanger overheats the metal, cycles the high-limit switch, and cracks heat exchangers over time. Fix the airflow — do not turn the gas down to hide it.

Furnace rise below the nameplate range. Either the blower is moving more air than the entered figure, or the furnace is firing below its rated input. Clock the gas meter and check manifold pressure before changing blower taps.

Target cooling split by return humidity

Target dry-bulb split at a 75 °F return, computed by the enthalpy method with 11,000 BTU/h delivered per nominal ton, 400 CFM per ton, and air leaving the coil at 95% RH. Rounded to the nearest half degree.
Return RHReturn wet bulb (°F)Target split (°F)Supply air (°F)
30%56.728.546.5
40%59.725.050.0
45%61.223.052.0
50%62.621.054.0
55%63.919.555.5
60%65.217.557.5
65%66.516.059.0
70%67.714.560.5

Change the capacity, airflow or return temperature above and the calculator rebuilds this table for your own assumptions. Manufacturer charging and performance data always take precedence over any generic table.

Things that corrupt a delta-T measurement

  • Reading too soon. A system needs 10–15 minutes of run time to settle. A reading taken at three minutes shows a wide split because the coil is still cold and the house is still hot.
  • Duct leakage between the probe and the equipment. A return that pulls 130 °F attic air through a leaking joint reads high, which narrows the apparent split and makes a healthy system look undercharged.
  • Radiant heat on the supply probe. On a furnace, a probe in line of sight of the heat exchanger reads well above the air temperature. Get past the first elbow.
  • Measuring a register instead of the plenum. Ducts in unconditioned space gain or lose heat on the way. Register temperature is what the room gets; plenum temperature is what the equipment made.
  • Assuming humidity instead of measuring it. The target moves by roughly 14 °F between 30% and 70% return RH in the table above. Guessing the humidity is the same as guessing the answer.
  • Diagnosing charge from delta-T alone. Delta-T is a symptom, not a diagnosis. It tells you to go measure something else — static pressure, superheat, subcooling — not what to adjust.

Never adjust refrigerant charge from delta-T

A wide or narrow split has at least four common causes, and only one of them is refrigerant charge. Adding refrigerant to fix a split that is actually caused by a dirty filter leaves you with a dirty filter and an overcharged system, which is worse than what you started with. Confirm airflow first, then charge by the manufacturer's method — subcooling for TXV and EEV systems, target superheat for fixed-orifice systems.

Where delta-T sits in a service call

Delta-T is a screening test. It is fast, non-invasive, and it costs nothing to take, so it belongs at the front of a diagnostic sequence rather than at the end of one.

A workable order on a cooling call: measure return dry bulb and humidity, measure supply dry bulb, and compare against the target here. If the split is off, measure total external static pressure and convert to airflow with the blower table — that separates the airflow causes from the refrigerant causes immediately. Only then connect gauges and take superheat and subcooling, which tell you what the refrigerant circuit is doing.

On a heating call the same logic runs in reverse: the temperature rise is the airflow measurement, provided you trust the nameplate output. Rearranging gives real CFM directly, which is often more reliable than a blower-table lookup because it does not depend on knowing the static pressure accurately.

If you want to work the airflow side of the same equation, the sensible heat calculator solves Q = 1.08 × CFM × ΔT in any direction, and the CFM per ton calculator checks the result against design airflow. For the humidity input, the wet bulb calculator converts between dry bulb, wet bulb and relative humidity.

Frequently asked questions

What should my AC delta-T be?

Between roughly 15 and 25 °F depending on how humid your return air is, with about 20–21 °F typical at 75 °F and 50% relative humidity. There is no single correct number: dry return air produces a wide split and humid return air a narrow one, on identical equipment working correctly. Measure the return humidity and read the target off the table above rather than comparing against a remembered figure.

Is a 25 degree delta-T too high?

It depends entirely on the return humidity. At 40% RH a 25 °F split is exactly on target. At 65% RH the same 25 °F is about 9 °F wide, which strongly suggests airflow below design. Measure total external static pressure and compare it against the blower table before drawing any conclusion; a 25 °F split with normal static pressure and dry indoor air is a healthy system.

Can low refrigerant charge cause a high delta-T?

Not usually — undercharge normally narrows the split, because the coil loses capacity while the airflow stays the same. A severe restriction in the liquid line or metering device can starve the coil enough to produce odd readings, but the classic undercharge signature is a narrow split with high superheat and low subcooling. A wide split with normal pressures points at airflow, not charge.

What temperature rise should a gas furnace have?

Whatever the data plate specifies, typically a 30–40 °F wide band somewhere between 25 and 70 °F. Compute the expected rise as output BTU/h divided by (1.08 × CFM) and compare. Running above the nameplate maximum overheats the heat exchanger and cycles the limit switch; running below it can cause condensation in a non-condensing furnace. The rise range is a code requirement, not a suggestion.

How long should the system run before I measure?

At least 10 to 15 minutes in cooling, and until the burners have been on for 5 to 10 minutes in heating. Cooling systems need time for the evaporator to reach a steady wet condition and for the refrigerant charge to distribute; the split narrows over the first few minutes and then stabilises. A furnace needs the heat exchanger up to temperature before the rise means anything.

Why does the calculator ask for capacity per ton instead of just the tonnage?

Because a nominal ton is a label, not a measurement. Equipment is rated at 12,000 BTU/h per ton at AHRI conditions — 80 °F dry bulb and 67 °F wet bulb entering the coil — and real return air is almost always cooler and drier than that, which lowers delivered capacity by several percent. Entering the capacity you actually expect keeps the target honest. If you have the manufacturer's expanded performance data for your return conditions, use that number.

Do heat pumps in heating mode use the same target?

No. A heat pump in heating produces a much smaller rise than a furnace — commonly 15 to 30 °F — because it delivers less heat through the same airflow, and the rise falls as outdoor temperature drops. Compare a heat pump's rise against the manufacturer's heating performance data at the current outdoor temperature, and remember that auxiliary electric heat energising will add its own rise on top.

Can I use a supply register instead of the plenum?

Only if the ducts run entirely inside conditioned space, and even then the reading is a few degrees off. Supply ducts in an attic or crawl space gain heat in summer and lose it in winter, so a register reading understates the split in cooling and understates the rise in heating. If plenum access is impossible, use the register closest to the air handler and note that your reading is conservative.

References

  • ASHRAE Handbook—Fundamentals, Chapter 1: Psychrometrics — American Society of Heating, Refrigerating and Air-Conditioning Engineers
  • ASHRAE Handbook—HVAC Systems and Equipment, Chapter 23: Air-Cooling and Dehumidifying Coils — American Society of Heating, Refrigerating and Air-Conditioning Engineers
  • ANSI Z21.47 / CSA 2.3, Gas-Fired Central Furnaces (nameplate temperature rise requirements) — American National Standards Institute / CSA Group
  • ACCA Standard 4, Maintenance of Residential HVAC Systems — Air Conditioning Contractors of America