Plumbing, Piping & Hydraulics Gas Piping & BTU Load NFPA 54 total connected load

Gas Appliance BTU Load Calculator

Everything downstream of a gas meter starts with one number: the total connected load, in BTU per hour, of every appliance the system feeds. That total sets the pipe size, decides whether the meter and service regulator are big enough, and tells you whether there is room for the dryer or generator you were thinking of adding. This calculator totals the appliance input ratings, converts them to cubic feet per hour at your gas heating value, and reports the result as a percentage of the meter capacity with the spare capacity in both CFH and BTU/hr.

Calculator

This calculator runs in your browser. Enable JavaScript for live results — the inputs, formula and worked example below remain fully readable without it.

Inputs this calculator takes, with typical values
InputWhat to enterExample
Furnace or boiler inputInput rating from the data plate, not the output or the AFUE-adjusted figure.80000 BTU/hr
Water heater input40,000 BTU/hr is a common tank heater; a tankless unit can be 150,000 to 199,000.40000 BTU/hr
Range or cooktop inputTotal of all burners plus the oven, from the rating plate behind the drawer.65000 BTU/hr
Clothes dryer inputResidential gas dryers are typically 20,000 to 25,000 BTU/hr.22000 BTU/hr
Fireplace or log set inputDirect-vent fireplaces are commonly 20,000 to 40,000 BTU/hr.30000 BTU/hr
Other appliancesGenerator, pool heater, outdoor kitchen, patio heater, second furnace - add their input ratings together here.0 BTU/hr
Gas heating valueHigher heating value of the gas. Confirm the natural gas figure with your utility if it matters.Natural gas - 1,030 BTU/ft3
Demand factorLeave at 100%. NFPA 54 sizes residential systems on the full connected load; diversity is only permitted where a code or utility rule specifically allows it.100 %
Meter or regulator rated capacityPrinted on the meter badge. A common residential diaphragm meter is rated 250 CFH.250 CFH

It returns

  • Total connected load — The figure pipe sizing and meter sizing both start from.
  • Design demand after demand factor
  • Gas flow required
  • Share of meter capacity used
  • Spare meter capacity
  • Spare capacity as heat

The formula

CFH=kQkHHV
U=CFHCFHmeter

In plain text: CFH = sum of appliance input ratings / heating value

  • CFHGas volume the system must deliver (ft3/hr)
  • QkInput rating of appliance k, from its rating plate (BTU/hr)
  • HHVHigher heating value of the gas: about 1,030 for natural gas, 2,516 for propane (BTU/ft3)

NFPA 54 sizes residential fuel gas piping on the total connected load - every appliance at full input, all at once - with no diversity allowance. That is deliberately conservative and it is what an inspector expects to see.

Updated Category Gas Piping & BTU Load Verified against published test cases Reading time 11 min

Connected load, and why nobody discounts it

Connected load is the sum of the input ratings of every gas appliance a system serves, assuming all of them fire at once. Nobody actually runs the furnace, the range, the dryer, the fireplace and the water heater simultaneously - but NFPA 54 sizes residential piping as though they did, and for a good reason: the consequence of being wrong is a starved burner, incomplete combustion and carbon monoxide, and the cost of being conservative is one pipe size.

Input rating is the gas an appliance consumes. It is not the output, and the difference is not small. A furnace advertised at 80,000 BTU/hr of heating output at 80% AFUE consumes 100,000 BTU/hr of gas. Size the pipe from the output figure and the system is undersized by a quarter. The rating plate always gives input, usually labelled Input or Gas input, and it is what you use.

The total is used in two separate checks. The pipe has to carry it - that is the pipe sizing problem, which also depends on developed length. And the meter and service regulator have to pass it, which is a straight capacity comparison and is what the utility cares about. A system can be perfectly piped and still be starved by a meter that was sized for the house before the tankless heater and the generator went in.

Once the load is in BTU per hour, converting to volume is a single division by the heating value of the gas. Natural gas is around 1,030 BTU per cubic foot, so a 237,000 BTU/hr house needs about 230 cubic feet an hour. Propane packs 2,516 BTU into a cubic foot, so the same house on propane needs only 94 CFH - one reason propane lines look small for the load they carry.

Reading the meter badge and the regulator rating

Every gas meter carries a badge with a capacity in cubic feet per hour at a stated pressure. Residential diaphragm meters in the common domestic size are typically rated 250 CFH, with larger ratings available for houses with heavy loads. The service regulator that sits ahead of the meter has its own capacity, and either can be the binding constraint.

Compare your calculated CFH against that rating. Below about 80% of it, you have real headroom. Between 80 and 100% the meter is technically adequate but nothing further can be added, and a utility may decline to approve a new appliance on it. Above 100% the meter must be changed before the appliances are connected, and no amount of pipe upsizing helps - a meter that cannot pass the flow will hold the downstream pressure down no matter how generous the pipe is.

Meter changes are the utility's work, not the installer's, and they usually take weeks rather than days. Doing this calculation before ordering equipment is the difference between a scheduled meter swap and a house with a new tankless heater that cannot be commissioned.

Watch the loads that move the total most. A tankless water heater at 199,000 BTU/hr is typically five times the tank heater it replaces and is the single most common cause of a meter suddenly being too small. A standby generator can add 150,000 to 250,000 BTU/hr. A pool heater can be 400,000. Each of these on its own can outweigh the entire rest of a house.

Worked example: a typical house, then the same house with a tankless heater

Start with the default house: an 80,000 BTU/hr furnace, a 40,000 BTU/hr tank water heater, a 65,000 BTU/hr range, a 22,000 BTU/hr dryer and a 30,000 BTU/hr direct-vent fireplace, on natural gas at 1,030 BTU per cubic foot through a 250 CFH meter.

  1. Total connected load. 80,000 + 40,000 + 65,000 + 22,000 + 30,000 = 237,000 BTU/hr.
  2. Convert to flow. 237,000 ÷ 1,030 = 230.1 CFH.
  3. Meter check. 230.1 ÷ 250 = 92.0% of the rated capacity.
  4. Spare. 250 − 230.1 = 19.9 CFH, which at 1,030 BTU per cubic foot is 20,500 BTU/hr - not enough for another dryer, and barely enough for a small log set.

Now replace the 40,000 BTU/hr tank heater with a 199,000 BTU/hr tankless unit. The connected load becomes 80,000 + 199,000 + 65,000 + 22,000 + 30,000 = 396,000 BTU/hr, which is 384.5 CFH. That is 154% of the 250 CFH meter. The pipe from the meter almost certainly needs upsizing as well, but the meter is the first problem and it is the utility's to solve.

The same arithmetic in reverse tells you what will fit. With 19.9 CFH spare on the original house, the largest appliance that could be added is 19.9 × 1,030 = 20,500 BTU/hr - a patio heater, perhaps, and nothing more.

What to do with the number

Take the CFH figure to two places. First to the pipe sizing calculation, where it becomes the flow the main from the meter has to carry over the developed length to the most remote appliance. Each downstream section is then sized on the load beyond it, so the branch to the range carries only the range.

Second, to the utility, if the meter check is tight. Ask for the meter and regulator ratings in writing rather than reading the badge through a decade of paint, and tell them the total connected load you have calculated. Utilities size their service on the same figure you have just produced.

If you want to know what the system is really drawing rather than what it could draw, clock the meter. With everything else off, time a known dial revolution while one appliance runs at full fire and convert to CFH - the method the gas meter clocking calculator sets out. That measures actual consumption and is the standard way to verify that an appliance is firing at its rated input, which is a different question from whether the system can carry it.

Finally, plan for the load you will have rather than the one you have. Adding a gas dryer, a generator, an outdoor kitchen or a pool heater later is straightforward if the meter and the main were sized with room, and an expensive retrofit if they were not. Enter the future appliances in the Other field now and see what it costs to allow for them.

Table-basis CFH and metered CFH are not the same number

This calculator's meter check uses the CFH implied by the heating value you selected - 1,030 BTU/ft³ for typical pipeline natural gas, or 2,516 for propane - because that is the actual volume the meter has to pass. NFPA 54's pipe-sizing capacity tables are built on a different assumption: the option in the heating-value list labelled ‘table basis, 1,000 BTU/ft³’ exists because that round number is what the published pipe-sizing tables are keyed to, not the true heating value of the gas itself.

The two figures diverge in a fixed direction. Dividing the same BTU/hr demand by 1,030 always gives a smaller CFH than dividing it by 1,000, because the divisor is larger. So a load run through this calculator at the actual heating value produces a CFH that sits a few percent below what the pipe-sizing tables expect for that same appliance load - the gap is the fixed ratio 1,000/1,030, regardless of how large the load is.

That difference is too small to change a meter decision, which is a straightforward capacity comparison at the real heating value. It matters when the same CFH number is carried over to look up a pipe size in NFPA 54's capacity tables: plugging in a CFH computed at 1,030 where the table's own columns assume 1,000 is one small step toward reading the table as though the load were lighter than it is. Recompute CFH at the table-basis value before the pipe-sizing lookup, and keep the actual-heating-value CFH for the meter check - the two answer different questions and neither substitutes for the other.

Typical input ratings for common gas appliances

Ranges seen on residential rating plates. Always use the actual plate figure - these are for planning before the equipment is chosen.
ApplianceTypical input (BTU/hr)Flow at 1,030 BTU/ft3 (CFH)
Furnace, mid-size residential60,000 - 100,00058 - 97
Boiler, residential80,000 - 150,00078 - 146
Storage water heater, 40-50 gal32,000 - 50,00031 - 49
Tankless water heater140,000 - 199,000136 - 193
Range with oven50,000 - 80,00049 - 78
Clothes dryer20,000 - 25,00019 - 24
Direct-vent fireplace20,000 - 40,00019 - 39
Standby generator, 12-22 kW150,000 - 250,000146 - 243
Pool or spa heater200,000 - 400,000194 - 388
Outdoor grill or patio heater30,000 - 60,00029 - 58

The CFH column is the BTU column divided by 1,030. On propane, divide by 2,516 instead, which gives about 41% of these figures.

Where load totals go wrong

  • Using output instead of input. The most common error and always in the unsafe direction. A furnace's input exceeds its output by the inverse of its efficiency.
  • Applying a diversity factor on residential work. NFPA 54 does not permit it. Multi-family and commercial systems sometimes do under specific utility rules, but a residential plan review will expect the full connected load.
  • Forgetting the appliance nobody thinks of. The fireplace in the basement, the garage heater, the outdoor grill on a quick-connect. Every one of them is connected load.
  • Checking pipe but not the meter. Pipe sizing and meter capacity are separate constraints. A correctly sized pipe fed by an overloaded meter still starves the appliances.
  • Mixing natural gas and propane figures. The heating values differ by a factor of about 2.4 and the specific gravities by 2.5. A propane system sized from natural gas tables will be wrong in both directions at once.
  • Assuming the utility's service is unlimited. The service regulator, the service line and sometimes the street main all have limits. A very large added load can require work well beyond the meter.

The code basis

NFPA 54, the National Fuel Gas Code (co-published as ANSI Z223.1 and reproduced in the International Fuel Gas Code), requires piping to be sized for the total connected load of all appliances served, using the input ratings marked on the appliances. Where an appliance is not yet selected, the code allows a load to be assumed and the piping sized for it. Demand factors and diversity are a feature of commercial and multi-family design under specific engineered methods, not of ordinary residential sizing. Work from the edition your jurisdiction has adopted, and remember that gas piping is licensed work almost everywhere.

Key terms

Connected load
The sum of the input ratings of every appliance served, with no allowance for the fact that they will not all run at once.
Input rating
The gas an appliance consumes at full fire, in BTU per hour, as marked on its rating plate. Always larger than the appliance's heat output.
CFH
Cubic feet of gas per hour. Connected load divided by the heating value of the gas.
Heating value
Heat released by burning one cubic foot of the gas. About 1,030 BTU/ft3 for pipeline natural gas and 2,516 BTU/ft3 for propane vapour.
Meter capacity
The maximum flow a meter can pass without excessive pressure loss, marked on the meter badge in CFH.

Frequently asked questions

How do I find an appliance's BTU input rating?

Look for the rating plate: behind the lower access panel on a furnace, on the side or under the top of a water heater, behind the bottom drawer on a range, and on the back of a dryer. The figure is marked Input and is given in BTU per hour, usually beside the gas type and the manifold pressure. If a plate is missing, the manufacturer's specification sheet by model number will have it.

What size gas meter do I need for my house?

The meter has to pass the total connected load converted to CFH, with margin. A typical house at 237,000 BTU/hr needs 230 CFH, which fits a 250 CFH residential meter with very little room to spare. Adding a tankless water heater or a standby generator commonly pushes a house past 250 CFH and requires the utility to fit a larger meter and possibly a larger service regulator.

Can I apply a diversity factor to residential gas load?

Not for code-compliant residential sizing. NFPA 54 asks for the total connected load with every appliance at full input, because the failure mode of an undersized system is incomplete combustion. Diversity is used in some multi-family and commercial engineered designs where a code provision or a utility rule specifically permits it, and in those cases the permitted factor comes from that rule rather than from judgement.

How many CFH is 100,000 BTU?

97.1 CFH on natural gas at 1,030 BTU per cubic foot, and 39.7 CFH on propane at 2,516 BTU per cubic foot. The conversion is a single division by the heating value. Natural gas figures are often quoted on a 1,000 BTU per cubic foot basis because the NFPA 54 capacity tables are built that way, which makes 100,000 BTU/hr exactly 100 CFH and is a convenient shortcut for rough work.

Does adding a tankless water heater need a new gas meter?

Often, yes. A 199,000 BTU/hr tankless unit adds about 193 CFH by itself, roughly five times a conventional tank heater, and that increase alone can exceed the spare capacity on a standard 250 CFH residential meter. Run the totals before ordering the unit, because a meter change is utility work with its own lead time and cannot be done by the installer.

What is the difference between connected load and demand?

Connected load is what would be drawn if everything ran at once. Demand is what is actually drawn at a given moment, which for a house is nearly always far less. Gas piping is sized on connected load; utility billing and load research use demand. In this calculator, leaving the demand factor at 100% makes the two figures identical, which is the code-compliant residential case.

Do I include an appliance I am planning to add later?

Include it if you want the piping and meter to accommodate it without rework. NFPA 54 permits sizing for an assumed future load, and doing so is far cheaper than replacing a main later. Enter the anticipated input rating in the Other field and see what it does to the meter percentage before deciding.

Why does propane need less flow than natural gas for the same appliance?

Because a cubic foot of propane carries about 2.4 times the heat of a cubic foot of natural gas, so far fewer cubic feet are needed for the same BTU per hour. That does not automatically make propane pipe smaller, because propane is also 2.5 times heavier and is distributed at different pressures - the two effects partly offset, and propane has its own sizing tables for exactly that reason.

References