Electrical Trade & Electronics Solar, Battery & Backup Power Peukert's law (IEC 61056 hour-rate basis)

Battery Runtime Calculator

Give this calculator a battery's amp-hour rating, its voltage, and the load in watts, and it returns the runtime in hours along with the discharge current, the amp-hours the battery will actually deliver at that current, and the C-rate. It applies three corrections that the naive amp-hours-divided-by-amps sum leaves out: the depth of discharge you are prepared to reach, inverter conversion losses, and Peukert's law, which is why a lead-acid battery that gives 100 Ah over twenty hours gives far less than 100 Ah over one hour.

Calculator

This calculator runs in your browser. Enable JavaScript for live results — the inputs, formula and worked example below remain fully readable without it.

Inputs this calculator takes, with typical values
InputWhat to enterExample
Battery or bank capacityNominal amp-hour rating at the manufacturer's published hour rate. For a bank, add the amp-hours of the parallel strings.100 Ah
Nominal voltageNominal bus voltage of the battery or bank. Use the bus voltage, not the resting terminal voltage.12 V
LoadContinuous power the load draws. For an AC load use the appliance's running watts, not its surge rating.300 W
Inverter efficiencyConversion efficiency between the battery and the load. Set it to 100 for a load wired directly to the DC bus.90 %
Depth of dischargeHow far down you will run the battery before stopping. Around 50% for lead-acid and 80-90% for LiFePO4.80 %
Peukert exponentSet 1.00 to ignore the effect, about 1.05 for LiFePO4, 1.1-1.2 for AGM and 1.2-1.3 for flooded lead-acid.1.05
Rated hour rateThe discharge duration the amp-hour rating was measured over — usually 20 h for deep-cycle lead-acid and 1 h for UPS cells.20 h

It returns

  • Runtime to the chosen depth of discharge — How long the load runs before the battery reaches the depth of discharge you set.
  • Discharge current at the battery
  • Amp-hours actually delivered at this current
  • Energy delivered to the load
  • C-rate of the discharge

The formula

t=DoDH(CIH)k
Ceff=IH(CIH)k
C-rate=IC

In plain text: t = DoD × H × (C / (I × H))^k, where I = P / (V × η)

  • tRuntime to the chosen depth of discharge (h)
  • DoDDepth of discharge you will reach (decimal)
  • HHour rate the capacity was measured at (h)
  • CNominal capacity at that hour rate (Ah)
  • IDischarge current at the battery terminals (A)
  • kPeukert exponent, 1.00 for an ideal battery (dimensionless)
  • PLoad power (W)
  • VNominal battery voltage (V)
  • ηInverter efficiency, 1.00 for a DC load (decimal)

At k = 1 the expression collapses to t = DoD × C / I, the familiar amp-hours divided by amps. Peukert's law was published for lead-acid cells and describes lithium chemistries only loosely, which is why exponents near 1.02-1.05 are used there.

Updated Category Solar, Battery & Backup Power Verified against published test cases Reading time 12 min

Why amp-hours divided by amps is the wrong answer

The runtime everyone reaches for first is capacity divided by current: 100 Ah at 10 A gives ten hours. That sum is right only when three things happen to be true — the load is wired straight to the battery, you intend to flatten the battery completely, and you are discharging at exactly the rate the manufacturer used to measure the rating. In a real installation none of the three usually holds.

An inverter sits in the path. A 300 W AC load behind a 90% efficient inverter pulls 300 ÷ 0.9 = 333 W from the battery, which at 12 V is 27.8 A, not 25 A. That extra current comes straight out of runtime: at a Peukert exponent of 1.00 the runtime falls by 1 − 25 ÷ 27.8 = 10%, and by more than that at any exponent above 1.

You stop well before empty. Lead-acid banks are normally worked to 50% of nominal capacity, LiFePO4 to 80-90%, and the inverter's low-voltage cut-out often intervenes before either. Runtime is proportional to the fraction you actually use.

Capacity itself depends on how fast you take it. This is the part that surprises people. A deep-cycle lead-acid battery labelled 100 Ah is measured over 20 hours at 5 A. Ask the same battery for 100 A and it will not give you one hour. Internal resistance and diffusion limits inside the plates mean it delivers about 74 Ah at an AGM exponent of 1.10 and about 47 Ah at a flooded exponent of 1.25 — 44 minutes down to 28 minutes, as the reference table below sets out. Peukert's law, published in 1897, captures that relationship with a single exponent.

This calculator applies all three corrections and reports the intermediate figures, so you can see which one is costing you the most.

Peukert's law and the terms around it

Start with the current the battery actually sees. Divide the load power by the battery voltage, and divide again by the inverter efficiency if the load is AC: I = P / (V × η). Everything downstream depends on this number, which is why a 48 V bank running the same appliance discharges at a quarter of the current a 12 V bank does — and therefore suffers far less Peukert penalty.

The Peukert term is a ratio raised to a power. Write the rating as a current: a 100 Ah battery rated over 20 hours corresponds to 5 A. The quantity C / (I × H) compares the nominal capacity to the amp-hours you would get if capacity were rate-independent. Raise it to the exponent k and multiply by H and you have the hours to full discharge.

The exponent is the whole story. At k = 1 the expression simplifies exactly to C / I and rate has no effect. Above 1, capacity shrinks as current rises above the rated current and grows as current falls below it — a battery discharged very slowly genuinely does yield more than its label. Flooded lead-acid sits around 1.2-1.3, AGM around 1.1-1.2, and LiFePO4 around 1.02-1.05, which is the main practical reason lithium behaves so much better under heavy loads.

Depth of discharge scales the answer linearly. Multiplying the full-discharge time by 0.5 gives the time to 50% depth of discharge. This is a close approximation rather than an identity, because the Peukert relation was fitted to complete discharges, but the error is small compared to the uncertainty in the exponent itself.

The hour rate matters as much as the exponent. A capacity quoted at the 20-hour rate and the same capacity quoted at the 1-hour rate describe very different batteries. UPS cells are usually rated over short periods; deep-cycle solar batteries over 20 hours, sometimes 100. Entering the wrong hour rate moves the answer more than most people expect, so take it from the datasheet.

Worked example: a 300 W load on a 100 Ah AGM battery

A van has a single 100 Ah AGM battery at 12 V, rated at the 20-hour rate, feeding a 300 W AC load through a 90% efficient inverter. The owner works the battery to 50% depth of discharge and the datasheet suggests a Peukert exponent of 1.20. Step through it:

  1. Battery current. 300 W ÷ (12 V × 0.90) = 300 ÷ 10.8 = 27.78 A.
  2. Rated current. 100 Ah ÷ 20 h = 5 A, so this discharge is about 5.6 times faster than the rating assumes.
  3. Capacity ratio. C ÷ (I × H) = 100 ÷ (27.78 × 20) = 100 ÷ 555.6 = 0.18.
  4. Raise to the exponent. 0.181.20 = 0.1277.
  5. Hours to full discharge. 20 × 0.1277 = 2.555 h.
  6. Apply depth of discharge. 2.555 × 0.50 = 1.277 h, or 1 hour 17 minutes.
  7. Amp-hours delivered. 27.78 A × 2.555 h = 71.0 Ah, against a nominal 100 Ah.
  8. Energy to the load. 300 W × 1.277 h = 383 Wh.

Compare that with the naive sum: 100 Ah × 12 V × 0.50 ÷ 300 W = 2.0 hours. The real answer is 1.277 hours — 36% less. Repeating the sum with a perfect inverter gives 1.449 h, so conversion losses account for (1.449 − 1.277) ÷ (2.000 − 1.277) = about a quarter of the gap and the Peukert effect for the remaining three quarters.

Change one input to see how much the chemistry matters. Set the exponent to 1.05, as for LiFePO4: 0.181.05 = 0.1652, so full discharge is 3.304 h and runtime at 50% is 1.652 h. Same amp-hours, same voltage, same load, 1.652 ÷ 1.277 = 29% more runtime.

How to read the result

Check the C-rate before you trust the runtime. The C-rate is the discharge current divided by the nominal capacity, so 0.25C empties a nominal capacity in four hours. Most deep-cycle lead-acid batteries are happy up to about 0.2C continuously; drum-style UPS cells and LiFePO4 tolerate 1C and more. If your C-rate is above the datasheet's maximum continuous discharge current, the runtime figure is academic — the battery, the BMS or the inverter will intervene first.

Watch for voltage sag, not just capacity. Under a heavy load the terminal voltage drops, and inverters shut down on low DC voltage. A 12 V lead-acid bank at 0.5C can sag near the typical 10.5 V cut-out while still holding real charge, so the practical runtime ends earlier than the arithmetic says. Larger conductors help: check yours against the voltage drop calculator, because a volt lost in the cable is a volt the inverter never sees.

Use the delivered amp-hours figure to judge the battery, not the runtime. Delivered capacity tells you what fraction of the label the load is actually reaching. If it comes back near the nominal rating, the discharge is gentle and the sizing is comfortable. If it comes back well under, either move to a higher bus voltage, add parallel capacity, or move to a chemistry with a flatter Peukert response.

Runtime and bank size are the same problem from two directions. If the answer is too short, the fix is more capacity, and the battery bank sizing calculator works the calculation backwards from the hours you need. For a system that recharges every day, size the array to replace what this calculator says you consumed.

Delivered capacity of a 100 Ah, 20-hour-rated battery

Amp-hours actually delivered at each discharge current, from C_eff = I × H × (C / (I × H))^k with C = 100 Ah and H = 20 h. The 5 A row is the rating point, where every exponent returns exactly 100 Ah.
Discharge currentC-ratek = 1.02 (LiFePO4)k = 1.10 (AGM)k = 1.25 (flooded)
5 A0.05C100.0 Ah100.0 Ah100.0 Ah
10 A0.10C98.6 Ah93.3 Ah84.1 Ah
20 A0.20C97.3 Ah87.1 Ah70.7 Ah
50 A0.50C95.5 Ah79.4 Ah56.2 Ah
100 A1.00C94.2 Ah74.1 Ah47.3 Ah

Read the exponent as a property of the chemistry and construction, not of the brand. Below the rating current the same formula returns more than 100 Ah, which is why a battery discharged over 100 hours can exceed its 20-hour label.

Assumptions and limits of this model

  • Peukert's law was fitted to lead-acid. It describes lithium iron phosphate only approximately; the flat voltage curve and low internal resistance of LiFePO4 mean an exponent near 1.02-1.05 is a convenient stand-in rather than a physical constant.
  • The model assumes a constant-power load. Real loads cycle. A fridge running a third of the time consumes a third of the energy, so use its average power, not its running power, for a duty-cycled appliance.
  • Temperature is not modelled. Lead-acid capacity falls in the cold and the effect is large enough to swamp the Peukert correction in a winter installation. Take the derating from the manufacturer's capacity-versus-temperature curve.
  • Age is not modelled. A battery at 80% state of health delivers 80% of these numbers. Deep-cycle batteries are commonly retired at that point.
  • Inverter efficiency varies with load. Datasheet efficiency is the peak of a curve, and good datasheets plot that curve against output power. Read your own load off it rather than using the headline number, because at very light loads the inverter's standby draw dominates and effective efficiency collapses.
  • Depth of discharge is applied linearly. Scaling the full-discharge time is an approximation to the Peukert relation, which was defined for complete discharges.

Where the hour rate comes from

Capacity ratings are only meaningful with their test duration attached, and that duration is set by standards rather than by marketing. IEC 61056 and IEC 60896 define the test conditions for general-purpose and stationary lead-acid batteries, and datasheets usually publish a table of C20, C10, C5 and C1 capacities for the same product. If you have that table, you do not need the Peukert exponent at all — read the capacity directly at the rate closest to your discharge, then interpolate. The exponent exists to fill the gap when only one figure is published, and you can derive it from any two published points: k = (log t₂ − log t₁) / (log I₁ − log I₂).

UPS runtime, vehicle house batteries and off-grid banks

The same formula serves three fairly different jobs, and knowing which one you are doing tells you what to worry about.

UPS backup. Here the discharge is short and hard — often 0.5C to 2C — so the Peukert correction dominates. UPS cells are rated over one hour or less for exactly that reason, and using a 20-hour rating for a UPS battery overstates its runtime badly. Check the manufacturer's constant-power discharge tables, which are given in watts per cell against minutes, in preference to any amp-hour arithmetic.

Vehicle and marine house batteries. Discharges are moderate and intermittent, and voltage sag through long undersized cable runs is often the real limit. Because these systems are usually 12 V, current is high for modest power, so upgrading the bus to 24 V is the cheapest single improvement available when loads grow. Confirm your conductor sizes with the wire size and ampacity calculator.

Off-grid house banks. Discharges are slow — often 0.02C to 0.1C overnight — so the Peukert penalty is small and the depth-of-discharge choice dominates. The question shifts from "how long will it last" to "how many cycles will I get", and that is set by cycle-life curves rather than by this formula.

If the load list is what you are unsure about, price the individual appliances first with the appliance energy cost calculator, and convert nameplate figures with the watts to amps calculator so every entry is in the same units before you add them up.

Frequently asked questions

How long will a 100 Ah battery run a 1,000 W load?

About 18 minutes on a 12 V lead-acid battery worked to 50% depth of discharge, against the 36 minutes the naive sum suggests. A 1,000 W load through a 90% inverter draws 1,000 ÷ (12 × 0.9) = 92.6 A, close to a 1C discharge; at a Peukert exponent of 1.2 the battery delivers about 56 Ah rather than 100 Ah, and half of that is available at 50% depth of discharge. Enter your own figures above — the chemistry exponent changes this answer substantially.

What is the Peukert exponent for my battery?

Use 1.02-1.05 for LiFePO4, 1.1-1.2 for AGM and gel, and 1.2-1.3 for flooded lead-acid, unless the datasheet gives you better information. If the datasheet publishes capacity at two different hour rates you can compute the exponent exactly: k = (log t₂ − log t₁) ÷ (log I₁ − log I₂), where each pair is a published current and its duration.

Should I set inverter efficiency to 100%?

Only if the load is wired directly to the DC bus — a 12 V fridge, LED lighting, or a DC water pump. Anything running on mains AC passes through an inverter, and 88-93% is typical for a good sine-wave unit at a healthy load. At very light loads the inverter's own idle consumption dominates: the datasheet gives it as a no-load draw in watts, and on a small load it can cost more than the conversion loss does. Take that figure from the datasheet and add it to your load rather than adjusting the efficiency.

Why does a higher system voltage give a longer runtime for the same amp-hours?

Because the same energy at a higher voltage means less current, and less current means less Peukert penalty and less resistive loss in the cable. A 100 Ah battery at 48 V holds four times the energy of a 100 Ah battery at 12 V, and it also delivers that energy at a quarter of the current for the same load, so the delivered fraction of nominal capacity is higher too.

Does this account for the battery being partly discharged already?

No — it assumes you start from full. If the battery is already at, say, 70% state of charge and you intend to stop at 20%, set the depth of discharge to the difference, 50%, and the answer is the remaining runtime from that point. The Peukert correction is applied to the full capacity in either case, which is a small approximation.

What C-rate is safe for continuous discharge?

Take it from the datasheet rather than a rule of thumb, because the range across products is wide. Deep-cycle flooded and AGM batteries are generally specified for continuous discharge around 0.2C, while LiFePO4 packs commonly permit 0.5C to 1C continuous and their internal battery management system enforces the limit. Exceeding the rating does not usually cause immediate damage, but it shortens life and increases voltage sag.

Why is my measured runtime shorter than this calculator predicts?

The three usual causes, in order of frequency: the battery has aged and no longer holds its rated capacity; the inverter cut out on low voltage before the target depth of discharge was reached, often because of voltage drop in undersized cable; or the load is larger than assumed because of standby draws you did not count. Measuring with a shunt-based monitor over a full discharge settles which one it is.

Can I use this for a UPS?

Yes, but change the hour rate. UPS cells are rated over short durations — often one hour or fifteen minutes — so entering their capacity against a 20-hour rate will overstate runtime badly. Better still, use the manufacturer's constant-power discharge table, which gives watts per cell against backup minutes and already includes the rate effect.

Does discharging more slowly really give more amp-hours?

Yes, for lead-acid. The same 100 Ah battery discharged over 100 hours typically yields more than its 20-hour rating, because the plates have time to diffuse and less of the capacity is lost to internal resistance. The formula reflects this: below the rated current the Peukert term exceeds one. The effect is small for LiFePO4, whose exponent is close to unity.

References

  • W. Peukert, 'Über die Abhängigkeit der Kapazität von der Entladestromstärke bei Bleiakkumulatoren', Elektrotechnische Zeitschrift 18 (1897) — Elektrotechnische Zeitschrift
  • IEC 61056, General purpose lead-acid batteries (valve-regulated types) — methods of test and requirements — International Electrotechnical Commission
  • Linden's Handbook of Batteries, 4th ed. — McGraw-Hill
  • IEEE Std 485, Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications — Institute of Electrical and Electronics Engineers